Reserve Power (VRLA - AGM & GEL, Pure Lead, and Flooded Tubular)

Critical Standby battery back-up applications where the energy is stored in reserve in batteries and ready for use whenever needed. Typical critical battery back-up applications are UPS (High rate applications), Telecom (long duration float application), Utility Switchgear (step loads, peak power shaving, frequency regulation, and distributed energy applications), Renewable Energy (cyclic solar/wind energy storage), Emergency Lighting (float applications), Industrial Controlled Power, Railway & Aircraft signal back-up support.

Leoch Battery Manufacturing has the most advanced manufacturing equipment and technology available today, with gravity cast grids, continuous punched grids, expanded metal grids, tubular grids, and the Premium Pure Lead punched grids for exceptional life and performance.

LPF Series - Front Terminal AGM

LPF Series - Front Terminal AGM for Telecom Applications

Designed for Standard 19" or 23 " relay racks and power cabinets / Network connection equipment of communication systems / Wireless and Wireline Telecom sites / local area network / Power stations systems / Excellent for APU (Aux Power Units) 

Front Terminal AGM - High Rate UPS Application:

Designed for UPS power cabinets requiring front terminals for easy maintenance recording /  Critical UPS, standby power supply,  APU – Aux Power Systems / Power station systems / Railway and marine systems.

 

LEOCH ASSURED TEL CATALOG

 

 

Additional Info

  • General Features:

    Capacity 40 to 190 AH - 136 to 783 WPC for 15 min to 1.67 VPC

    Virgin lead plates w/ copper alloy terminal inserts (low resistance)

    Easy Access to front terminals speeds voltage & ohmic readings

    Solid ABS jar and cover (UL94V-0 Flame Retardent available)

    Strong gravity casted grids for long life

    Designed for crtitical telecom and critical high rate UPS applications - 10-12 year design life

    100% initial capacity and streamlined design speeds installation

    UL recognized, IEC60896-21 & 22 certified and IATA approved for air freight

  • Specifications (Click on the link to see PDF):
    Model

     Nominal   Voltage

    (V) 
    Rated Capacity(AH) Approx Dimension Approx
    Weight
    Terminal type
    10HR 8HR 5HR 1HR Length Width Height Total Height
    1.80 1.80 1.75 1.67 mm in. mm in. mm in. mm in. kg lbs
    V/cell V/cell V/cell V/cell
    LPF12-40 12 41.5 40.0 37.8 27.7 277 10.9 106 4.17 222 8.74 222 8.74 15.5 34.2 T6
    LPF12-50 12 50.0 48.0 43.8 32.0 390 15.3 105 4.17 200 7.87 200 7.87 18.3 40.4 T6
    LPF12-55 12 55.0 53.0 50.1 36.7 277 10.9 106 4.17 222 8.74 222 8.74 17.3 39.7 T6
    LPF12-70 12 70.0 67.4 61.5 46.3 564 22.2 114 4.49 187 7.36 187 7.36 25.5 56.2 T6
    LPF12-75 12 75.0 73.1 65.5 49.5 564 22.2 114 4.49 187 7.36 187 7.36 26.0 57.3 T6
    LPF12-90 12 94.4 90.0 82.0 61.4 508 20.0 110 4.33 238.5 9.39 238.5 9.39 32.0 70.6 T13
    LPF12-100A 12 100 95.2 87.0 63.7 508 20.0 110 4.33 238.5 9.39 238.5 9.39 35.0 77.2 T13
    LPF12-100H 12 100 95.2 87.0 64.4 394 15.5 110 4.33 285 11.2 285 11.2 34.5 76.1 T6
    LPF12-125 12 125 119.2 108.5 80.1 551 21.7 110 4.33 287 11.3 287 11.3 41.5 91.5 T6
    LPF12-150A 12 150 142.4 130.5 95.9 551 21.7 110 4.33 287 11.3 287 11.3 46.8 102.3 T6
    LPF12-150B 12 150 142.4 130.5 97.5 560 22.0 110 4.33 280 11.0 280 11.0 46.0 101.4 T13
    LPF12-165 12 170 160.8 148.0 110.5 560 22.0 126 4.96 280 11.0 280 11.0 54.0 119.1 T13
    LPF12-190 12 200.0 192.0 173.0 131.2 560 22.05 126 4.96 320 12.6 320 12.6 60.0 132.3 T11